6. Specifications
Voltage
Range
Low Line Loss 110 VAC ± 3 % at 50% Load; 176 VAC ± 3 % at 100% Load
Frequency Range
56Hz ~ 64 Hz @ 60Hz system
Output voltage 208/220/230/240VAC
AC Voltage Regulation ± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
Overload
AC mode
110%~130%: 1min
>130% : 1sec
Battery mode
110%~130%: 10sec
>130% : 1sec
≦
≦
Transfer
Time
Line Battery 0 ms
Inversor Bypass 0 ms
Standard
Model
Recharge Time
90% capacity
90% capacity
capacity
capacity
Long-run
Model
Depending on applications
Standard
Model
Dimension, D X W X H 592X250X576
580X438X133
Battery pack: 580X438
X133
592 X250 X576
668X438X133
Battery pack: 580X438
X133
Net Weight (kgs) 81
Battery pack: 57
83
Battery pack: 63
Model
the battery life will down when > 25
rts Windows®2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.